NYIFY
300/500 V Multi Core,Solid or Stranded copper conductor , PVC insulated , installation cables
Standart
VDE 0250, IEC 60227,
Technical Information
Max. Operating Temperature : 70 °C
Max. Short circuit temperature : 160°C
rated Voltage : 300/500 V
Cable Construction
- Solid or Stranded copper conductor
- PVC insulation
- PVC outer sheath
Application
The cable is suitable for nail driving, and is used as the mains, lighting and power cable. It is used in indoor and outdoor areas where there is not much mechanical stress.
Nominal cross-section |
Overall diameter (Approx) |
Net Weight (Approx) |
Delivery Lenght |
Conductor DC Resistance |
Current carrying capacity in | |
mm² | mm | kg/km | m | ohm/km | In conduit at 20°C A | In air at 30°C A |
2x1 | 3,3x9,6 | 44 | 100 | 18,1 | - | 12 |
2x1,5 | 3,8x12,5 | 65 | 100 | 12,1 | - | 18 |
2x2,5 | 4,6x14,1 | 95 | 100 | 7,41 | - | 26 |
2x4 | 6,2x15,5 | 130 | 100 | 4,61 | - | 34 |
3x1 | 3,3x10,1 | 65 | 100 | 18,1 | - | 12 |
3x1,5 | 3,8x21,3 | 100 | 100 | 12,1 | - | 18 |
3x2,5 | 4,6x23,7 | 145 | 100 | 7,41 | - | 26 |
3x4 | 6,2x25,0 | 191 | 100 | 4,61 | - | 34 |