HO5V-U / H07V-U

300/500 V, 450/750 V PVC Insulated Installation Cables

Standard
TS EN 50525-2-31, HD 21.3 S3, BS 6004, VDE 0281

Technical Information
Max. Operating Temperature : 70 °C
Max. Short circuit temperature : 160°C
Rated Voltage : 300/500 V

Cable Construction
1. Solid copper conductor
2. PVC insulation

Application
In dry rooms switch and distribution boards , for lying in conduit on and under plaster and on insulating support above plaster

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
1 2,5 14 100 18,1 11 19
1,5 2,8 20 100 12,1 16 25
2,5 3,4 31 100 7,41 21 34
4 3,9 46 100 4,61 27 45
6 4,4 54 100 3,08 35 57
10 5,6 108 100 1,83 48 78