H05V-K / H07V-K

300/500 V, 450/750 V PVC Insulated Installation Cables

Standard
TS EN 50525-2-31, HD 21.3 S3, BS 6004, VDE 0281

Technical Information
Max. Operating Temperature  : 70 °C
Max. Short circuit temperature : 160°C
rated Voltage : 300/500 V, 450/750V

Cable Construction

  1. Flexible copper conductor
  2. PVC insulation

Application
In dry rooms switch and distrubution boards , for lying inconduit on and under plaster and on insulating support above plaster

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
0,5 2,1 9 100 39 - -
0,75 2,3 11 100 26 - -
1 2,5 14 100 19,5 12 20
1,5 3 20 100 13,3 15 24
2,5 3,6 32 100 7,98 20 32
4 4,2 48 100 4,95 25 42
6 4,8 68 100 3,3 33 54
10 6,7 116 100 1,91 45 73
16 7,9 174 100 1,21 61 98
25 9,7 270 1000 0,78 83 129
35 11,1 368 1000 0,554 103 158
50 13,3 524 1000 0,386 132 198
70 15,2 717 1000 0,272 165 245
95 17,7 971 1000 0,206 197 292
120 19,6 1212 1000 0,161 235 344
150 21,9 1514 1000 0,129 391
185 24,3 1869 1000 0,106 448
240 27,5 2415 1000 0,0801 528