YAVZ3V(NAYFGBY)

0.6/1 kV, Multi core,Stranded Aluminium conductor, PVC Insulated, Flat Steel wire Armour , PVC outer sheath, LV power cables

Standard
TS IEC 60502-1, IEC 60502

Technical Data 

Max.Operating Temperature: 70 ° C

Max.Short Circuit Temperature: 160 ° C

Rated Voltage:, 0,6/1 kV

Construction 

  1. Stranded Aluminium conductor
  2. PVC insulation
  3. PVC filler
  4. Galvanized Flat Steel Wire Armour
  5. PVC outer Sheath

Application 
Is most suitable ares where mechanical damage is a possibility . Is laid outdoors , indoors underground and in ducts. If requested can be produced to resist saline environment

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
3x16 23 1000 1000 1,91 66 64
3x25 26 1300 1000 1,2 99 83
3x35 29 1650 1000 0,68 118 102
3x50 31,5 2000 1000 0,641 142 124
3x70 36 2500 500 0,443 176 158
3x95 40,5 3100 500 0,32 211 160
3x120 44 3600 500 0,253 242 220
3x150 50 4500 500 0,206 270 252
3x185 52 5150 500 0,164 308 290
3x240 60 6500 500 0,125 363 339
3x300 66 7800 500 0,1 412 377
3x25+16 27 1450 1000 1,20-1,91 99 83
3x35+16 29 1650 1000 0,868-1,91 118 102
3x50+25 33 2100 1000 0,641-1,20 142 124
3x70+35 38 2700 1000 0,443-0,868 176 158
3x95+50 42,5 3350 500 0,320-0,641 211 160
3x120+70 47 4000 500 0,253-0,443 242 220
3x150+70 51,5 4700 500 0,206-0,443 270 252
3x185+95 54,5 5500 500 0,164-0,320 308 289
3x240+120 62 6850 500 0,125-0,253 363 339
3x300+150 68,5 8300 500 0,100-0,206 412 377
4x16 25 1200 1000 1,91 66 64
4x25 28 1550 1000 1,2 99 83
4x35 30,5 1800 1000 0,68 118 102
4x50 35 2350 1000 0,641 142 124
4x70 40 2900 500 0,443 176 158
4x95 44,5 3650 500 0,32 211 160
4x120 49 4300 500 0,253 242 220
4x150 55 5300 500 0,206 270 252
4x185 58 6150 500 0,164 308 289
4x240 66,5 650 500 0,125 363 339
4x300 73 9250 500 0,1 412 377