YVV(NYY Control Cables)

0.6/1 kV Multi core , Solid or Stranded copper , PVC insulated cables 

Standard
TS IEC 60502-1, IEC 60502

Technical Data 

Max.Operating Temperature: 70 ° C

Max.Short Circuit Temperature: ≤ 300 mm² 160°C , >300 mm² 140 °C

Rated Voltage:, 0,6/1 kV

Construction 

  1. Solid or stranded copper conductor
  2. PVC insulation
  3. PVC filler
  4. PVC Outer sheath

Application
Is used as control cable in power stations and factories where signalling is required . Can be laid in doors , our-doors , buried or in cable dutch

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
5x1,5 13 270 1000 12,1 18 14
7x1,5 14 320 1000 12,1 16 12
10x1,5 17 470 1000 12,1 13 10
12x1,5 18 520 1000 12,1 12 10
14x1,5 19,5 570 1000 12,1 12 9
19x1,5 20 700 1000 12,1 10 8
21x1,5 21 780 1000 12,1 10 8
24x1,5 23 920 1000 12,1 9 7
30x1,5 25 1060 1000 12,1 9 7
40x1,5 27 1350 1000 12,1 8 7
48x1,5 30 1600 1000 12,1 7 6
61x1,5 33 2000 1000 12,1 7 6
5x2,5 14 350 1000 7,41 24 19
7x2,5 15 420 1000 7,41 20 16
10x2,5 19 620 1000 7,41 17 14
12x2,5 19,5 680 1000 7,41 16 13
14x2,5 20 750 1000 7,41 15 13
19x2,5 22 950 1000 7,41 14 11
21x2,5 23 1050 1000 7,41 13 11
24x2,5 26 1250 1000 7,41 12 10
30x2,5 27 1430 1000 7,41 11 9
40x2,5 30 1850 1000 7,41 10 9
48x2,5 34 2250 1000 7,41 10 8
61x2,5 37 2750 1000 7,41 9 8