YAVZ2V(NAYRY)

0.6/1 kV, Multi core, Stranded Aluminium conductor, PVC Insulated, Steel wire Armour , PVC outer sheath, LV power cables

Standard
TS IEC 60502-1, IEC 60502

Technical Data 

Max.Operating Temperature: 70 ° C

Max.Short Circuit Temperature: 160 ° C

Rated Voltage:, 0,6/1 kV

Construction 

  1. Solid or stranded Aluminium conductor
  2. PVC insulation
  3. PVC filler
  4. Galvanized Steel Wire Armour
  5. PVC outer Sheath

Application 
Is most suitable ares where mechanical damage is a possibility . Is laid outdoors , indoors underground and in ducts. If requested can be produced to resist saline environment

ılır.

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
3x16 23 1070 1000 1,91 66 64
3x25 27 1550 1000 1,2 99 83
3x35 30 1850 1000 0,68 118 102
3x50 33 2200 1000 0,641 142 124
3x70 38 3050 500 0,443 176 158
3x95 42,5 3700 500 0,32 211 160
3x120 46 4250 500 0,253 242 220
3x150 52,5 5700 500 0,206 270 252
3x185 55 6420 500 0,164 308 290
3x240 63 7800 500 0,125 363 339
3x300 69 9400 500 0,1 412 377
3x25+16 28 1650 1000 1,20-1,91 99 83
3x35+16 30,5 1900 1000 0,868-1,91 118 102
3x50+25 35 2600 1000 0,641-1,20 142 124
3x70+35 39,5 3250 1000 0,443-0,868 176 158
3x95+50 44,5 4000 500 0,320-0,641 211 160
3x120+70 50 5150 500 0,253-0,443 242 220
3x150+70 54,5 6000 500 0,206-0,443 270 252
3x185+95 57 6850 500 0,164-0,320 308 289
3x240+120 65 8400 500 0,125-0,253 363 339
3x300+150 71,5 10000 500 0,100-0,206 412 377
4x16 26 1350 1000 1,91 66 64
4x25 29 1750 1000 1,2 99 83
4x35 31,5 2050 1000 0,68 118 102
4x50 37 2900 1000 0,641 142 124
4x70 41,5 3550 500 0,443 176 158
4x95 48 4750 500 0,32 211 160
4x120 52 5500 500 0,253 242 220
4x150 58 6700 500 0,206 270 252
4x185 61 7650 500 0,164 308 289
4x240 69,5 9350 500 0,125 363 339
4x300 76 11050 500 0,1 412 377