H07Z1-R
450/750 V Stranded copper conductor, Halogen Free , Flame Retardant cables
Standard
TS EN 50525-3-31, BS 7211, VDE 250
Technical Information
Max. Operating Temperature : 90 °C
Max. Short circuit temperature : 250°C
Rated Voltage : 450/750V
Cable Construction
- Stranded copper conductor
- Eva based insulation
Application
It is used in hospitals, shopping centers, large hotels, facilities with a high fire risk, in dry and closed places, under plaster or over plaster. These cables do not transmit flame during fire, do not create smoke density . They provide life and property safety.
Nominal cross-section |
Overall diameter (Approx) |
Net Weight (Approx) |
Delivery Lenght |
Conductor DC Resistance |
Current carrying capacity in | |
mm² | mm | kg/km | m | ohm/km | In conduit at 20°C A | In air at 30°C A |
1,5 | 3,0 | 22 | 100 | 13,3 | 15 | 24 |
2,5 | 3,6 | 34 | 100 | 7,98 | 20 | 31 |
4 | 4,2 | 50 | 100 | 4,95 | 25 | 41 |
6 | 4,8 | 50 | 100 | 4,95 | 33 | 53 |
10 | 6,7 | 120 | 100 | 1,91 | 45 | 73 |
16 | 7,9 | 179 | 100 | 1,21 | 61 | 98 |
25 | 9,7 | 277 | 100 | 0,78 | 83 | 129 |
35 | 11,1 | 376 | 100 | 0,554 | 103 | 158 |
50 | 13,3 | 335 | 100 | 0,386 | 132 | 198 |
70 | 15,2 | 730 | 100 | 0,272 | 165 | 245 |
95 | 17,7 | 988 | 100 | 0,206 | 197 | 292 |
120 | 19,6 | 1231 | 100 | 0,161 | 235 | 344 |
150 | 21,9 | 1538 | 100 | 0,129 | - | - |
185 | 24,3 | 1899 | 100 | 0,106 | - | 448 |
240 | 27,5 | 2453 | 100 | 0,0801 | - | 528 |