H05Z1-U, H07Z1-U

300/500 V and 450/750 V Solid, Halogen Free , Flame Retardant Cables

Standart
TS EN 50525-3-31, VDE 250

Technical Information
Max. Operating Temperature  : 90 °C
Max. Short circuit temperature : 250°C
Rated Voltage : 300/500 V, 450/750 V

Cable Construction

  1. Solid  copper conductor
  2. Eva based insulation

Application
It is used in hospitals, shopping centers, large hotels, facilities with a high fire risk, in dry and closed places, under plaster or over plaster. These cables do not transmit flame during fire, do not create smoke density . They provide life and property safety.

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
0,5 2,1 9 100 36 3 12
0,75 2,3 12 100 24,5 6 15
1 2,5 15 100 18,1 11 19
1,5 2,8 21 100 12,1 16 24
2,5 3,4 33 100 7,41 21 32
4 3,9 48 100 4,61 27 43
6 4,4 68 100 3,08 34 54
10 5,6 112 100 1,83 47 74