YXV (N2XY KUMANDA)

0.6/1 kV Single or Multi core , Solid or Stranded copper conductor, XLPE insulation LV power cables

Standard
TS IEC 60502-1, IEC 60502, BS 7889, NFC 32-321

Technical Data 

Max.Operating Temperature: 90 ° C

Max.Short Circuit Temperature: 250 ° C

Rated Voltage:, 0,6/1 kV

Construction 

  1. Solid or stranded copper conductor
  2. XLPE insulation
  3. PVC filler
  4. PVC Outer sheath

Applications
These cables with low dielectric loss are used in energy facilities where sudden load changes occur in residential and industrial areas, outside, under the ground and in cable ducts.

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
5x1,5 12 250 1000 12,1 21 18
7x1,5 13 300 1000 12,1 18 16
10x1,5 16 450 1000 12,1 15 13
12x1,5 16 460 1000 12,1 14 13
14x1,5 17 510 1000 12,1 14 12
19x1,5 19 640 1000 12,1 12 11
21x1,5 20 700 1000 12,1 11 10
24x1,5 22 850 1000 12,1 11 10
30x1,5 23 950 1000 12,1 10 9
40x1,5 26 1200 1000 12,1 9 8
48x1,5 28 1450 1000 12,1 8 8
61x1,5 31 1800 1000 12,1 8 7
5x2,5 13 310 1000 7,41 28 24
7x2,5 14 390 1000 7,41 24 21
10x2,5 18 570 1000 7,41 20 18
12x2,5 18 620 1000 7,41 19 17
14x2,5 19 690 1000 7,41 18 16
19x2,5 21 870 1000 7,41 16 14
21x2,5 22 950 1000 7,41 15 14
24x2,5 24 1150 1000 7,41 14 13
30x2,5 26 1300 1000 7,41 13 12
40x2,5 29 1700 1000 7,41 12 11
48x2,5 32 2100 1000 7,41 11 11
61x2,5 34 2500 1000 7,41 10 10