N2XH FE 180 (CONTROL)

0.6/1 kV ,Multi core ,Solid or Stranded copper conductor, Mica Tape , XLPE insulation, Halogen Free , Flame Retardant Cables LV Power Cable

Standard
TS HD 604 S1 , VDE 0276

Technical Data 

Max.Operating Temperature: 90 ° C

Max.Short Circuit Temperature: 250 ° C

Rated Voltage:, 0,6/1 kV

Construction 

  1. Solid or stranded copper conductor
  2. Mica Tape
  3. XLPE insulation
  4. Halogen Free filler
  5. EVA/PR based Outer sheath

Application
Refineries, mines, hotels, schools, tunnels, high-rise buildings, hospitals, power plants, data processing centers, business centers and fire-sensitive areas.

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
5x1,5 16,0 270 1000 12,1 21 18
7x1,5 17,0 330 1000 12,1 18 16
10x1,5 21,0 470 1000 12,1 15 13
10x1,5 21,0 470 1000 12,1 14 13
14x1,5 23,0 570 1000 12,1 14 12
19x1,5 25,0 700 1000 12,1 12 11
21x1,5 27,0 750 1000 12,1 11 10
24x1,5 30,0 950 1000 12,1 11 10
30x1,5 32,0 1100 1000 12,1 10 9
40x1,5 35,0 1400 1000 12,1 9 8
48x1,5 39,0 1700 1000 12,1 8 8
61x1,5 43,0 2050 1000 12,1 8 7
5x2,5 17,0 340 1000 7,41 28 24
7x2,5 19,0 420 1000 7,41 24 21
10x2,5 23,0 600 1000 7,41 20 18
12x2,5 24,0 700 1000 7,41 19 17
14x2,5 25,0 750 1000 7,41 18 16
19x2,5 28,0 950 1000 7,41 16 14
21x2,5 29,0 1050 1000 7,41 15 14
24x2,5 32,0 1250 1000 7,41 14 13
30x2,5 35,0 1500 1000 7,41 13 12
40x2,5 39,0 1900 1000 7,41 12 11
48x2,5 43,0 2300 1000 7,41 11 11
61x2,5 47,0 2800 1000 7,41 10 10